Hello, Mark,
this is the protocol file Ralph was talking about. We have that in the field:
epics@fel-aes:~/FHI/IOCVAC/IOCVACApp/Db$ more multigauge.proto
# MultiGauge Compatible protocol for the Varian Dual Controller
# Pete Owens 22-1-02
# Ralph Lange 19-08-11
terminator = CR;
replytimeout = 1000;
readtimeout = 1000;
extrainput = Ignore;
# this protocol is just for testing
raw { out "#\$1" "000"; in "%s"; }
vmeas { out "#\$1" "07?"; in ">\$1" "07%d"; }
imeas { out "#\$1" "08?"; in ">\$1" "08%f"; }
pmeas { out "#\$1" "02?"; in ">\$1" "02%f"; }
rsetpt1 { out "#\$1" "71?"; in ">\$1" "71%f"; }
wsetpt1 { out "#\$1" "71%0.1E"; in ">\$1" "71"; }
rsetpt2 { out "#\$1" "72?"; in ">\$1" "72%f"; }
wsetpt2 { out "#\$1" "72%0.1E"; in ">\$1" "72"; }
whvpwr { out "#\$1" "30%1b"; in ">\$1" "00"; }
rhvpwr { out "#\$1" "30?"; in ">\$1" "30%1b"; }
dtype { out "#\$1" "11?"; in ">\$1" "11%s"; }
I saw that you made some useful changes. I will try these out on occasion.
Heinz
> On 2. Mar 2020, at 16:28, Mark Rivers via Tech-talk <tech-talk at aps.anl.gov> wrote:
>
> Hi Ralph and Pete,
>
> Thanks very much for those.
>
> I have fixed some problems and added some new PVs.
>
> My version is in the synApps ip module: https://github.com/epics-modules/ip
>
> The files are
> ipApp/Db/VarianDualIP.db
> ipApp/Db/VarianDualIP.protocol
> ipApp/Db/VarianDaulIP_settings.req
> ipApp/op/adl/VarianDualIP.adl
> ipApp/op/*/autoconvert/VarianDuallIP.*
>
> Thanks,
> Mark
>
>
> From: Ralph Lange <ralph.lange at gmx.de>
> Sent: Friday, February 28, 2020 10:52 AM
> To: Mark Rivers <rivers at cars.uchicago.edu>
> Subject: Fwd: Streams Support for Varian Dual
>
> Here's what I got from Pete for Heinz' FEL project nine years ago. :-)
> I probably updated them for the FEL, but I don't have access to their system anymore. Heinz will know - he's on vacation and I don't know when he will be back.
>
> Cheers,
> ~Ralph
>
> ---------- Forwarded message ---------
> From: <peter.owens at stfc.ac.uk>
> Date: Fri, 22 Jul 2011 at 19:02
> Subject: RE: Streams Support for Varian Dual
> To: <Ralph.Lange at gmx.de>
>
>
> Hi Ralph,
>
> Here are the original files.
>
> Pete
>
> -----Original Message-----
> From: Ralph Lange [mailto:Ralph.Lange at gmx.de]
> Sent: 22 July 2011 13:02
> To: Owens, Peter (STFC,DL,TECH)
> Subject: Streams Support for Varian Dual
>
> Hi Pete,
>
> you are listed in the EPICS Support database as contact for the Streams
> support for Varian Dual Ion Pump Controllers.
>
> Do you have something that you can tar up to get me started?
>
> Thanks a lot,
> Ralph
>
> --
> Scanned by iCritical.
>
- Replies:
- RE: Streams Support for Varian Dual Mark Rivers via Tech-talk
- References:
- RE: Streams Support for Varian Dual Mark Rivers via Tech-talk
- Navigate by Date:
- Prev:
Re: pco Camera USB and IEEE interface Mark Rivers via Tech-talk
- Next:
EPICS connection with S7-1500 PLC Vishnu Patel via Tech-talk
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
2017
2018
2019
<2020>
2021
2022
2023
2024
- Navigate by Thread:
- Prev:
RE: Streams Support for Varian Dual Mark Rivers via Tech-talk
- Next:
RE: Streams Support for Varian Dual Mark Rivers via Tech-talk
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
2017
2018
2019
<2020>
2021
2022
2023
2024
|